| SENTRON, meas. device & power quality recorder, 7KM PAC5200, standard rail housing w/o display L-L: 690 V, L-N: 400 V, 10 A, strd rail instr., 3- phase, Modbus TCP, apparent/ Active/reactive energy / cos phi, harmonics: 2. - 40., THD, class 0.5 acc. to IEC61557-12 or cl. 0.5S acc. to IEC62053-22, wide-range pwr sup. unit AC/DC, screw terminals |
| Model |
| Product brand name | SENTRON |
| Product designation | 7KM PAC5200 |
| Design of the product | Advanced |
| Product type designation | Measuring instrument and power quality recorder |
| Type of measured value detection | complete |
| Design of the power supply | Wide-range power supply |
| General technical data |
| Size of Power Monitoring Device / company-specific | DIN rail |
| Operating mode for measured value detection | |
| automatic line frequency detection | Yes |
| set at 50 Hz | No |
| set to 60 Hz | No |
| Pulse duration | |
| initial value | 50 ms |
| Full-scale value | 3 600 000 ms |
| Voltage curve | Sinusoidal or distorted |
| Measurable line frequency / initial value | 45 Hz |
| Measurable line frequency / Full-scale value | 65 Hz |
| Measuring procedure / for voltage measurement | TRMS |
| Supply voltage |
| Type of voltage / of the supply voltage | AC/DC |
| Measuring category / for supply voltage | CATIII |
| Apparent power consumption | |
| with expansion module / maximum | 6 V·A |
| without expansion module / typical | 6 V·A |
| Relative symmetrical tolerance / of the supply voltage | 20 % |
| Protection class |
| Protection class IP | |
| on the front | IP20 |
| Rear side | IP20 |
| Operating resource protection class / when installed | II |
| Electricity |
| Measurable current / 2 / at AC / Rated value | 10 A |
| Suitability |
| Suitability for operation | Standard mounting rail device |
| Adjustable time period / minimum | 50 ms |
| Product function |
| Product function | |
| Illuminance of display backlighting adjustable | No |
| Time-controlled reduction of the illuminance of display backlighting possible | No |
| reactive power measurement | Yes |
| frequency measurement | Yes |
| pulse measurement | Yes |
| Display contrast adjustable | No |
| voltage measurement | Yes |
| Current measurement | Yes |
| active power measurement | Yes |
| Display and operation |
| Design of the display | Standard mounting rail enclosure without display |
| Number of keys | 4 |
| Color / of the background of the display | white |
| National language / on the display screen / is supported | de, en |
| Product function / Display can be inverted (positive <=> negative mode) | No |
| Communication |
| Refresh time / at the interface | |
| maximum | 1 s |
| Number of interfaces / acc. to Fast Ethernet | 1 |
| Design of cable / connectable / Twisted pair | Yes |
| Protocol | |
| is supported | Modbus TCP |
| Fault limits |
| Reference condition / for metering accuracy | according to IEC 62053-22, IEC 62053-23, IEC 62586-1, Class S, IEC 61000-4-30, IEC 61000-4-7, IEC 61000-4-15 |
| Formula for relative total measurement inaccuracy | |
| for measured variable reactive energy | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| for measured variable output | +/- 0,5 % |
| for measured variable output factor | +/- 0,5 % |
| for measured variable voltage | +/- 0,2 % |
| for measured variable current | +/- 0,2 % |
| for measured variable THD | +/- 0.5 % |
| for measured variable active energy | Cl. 0.5 acc. to... IEC62053-22 |
| Inputs Outputs |
| Number of digital outputs | 2 |
| Digital output version | Continuous output, pulse output |
| Type of switching output | solid state |
| Type of electrical connection | |
| at the digital outputs | screw-type terminals |
| Output current | |
| at digital output / for signal <1> / minimum | 100 mA |
| at digital output / for signal <1> / maximum | 300 mA |
| at the digital outputs / at DC / maximum | 100 mA |
| Operating voltage / as output voltage / at DC / maximum permissible | 250 V |
| Property of the output / Short-circuit proof | Yes |
| Internal resistance / at the digital outputs | 35 Ω |
| Measuring category / for digital signals | Cat. III |
| Switching frequency / at digital output / maximum | 10 Hz |
| Transfer rate | |
| 1 / for fast Ethernet | 10 Mbit/s |
| 2 / for fast Ethernet | 100 Mbit/s |
| Measuring inputs |
| Outer conductors and neutral conductors internal resistance / for voltage measurement | 6 MΩ |
| Measurable supply voltage | |
| between (PE)N and L / at AC / maximum rated value | 400 V |
| between the outer conductors / at AC / maximum | 831 V |
| between the outer conductors / at AC / maximum rated value | 690 V |
| Voltage measuring range extension / with external voltage transformers | Yes |
| Current measuring range extension / with external current transformers | Yes |
| Measuring category / for voltage measurement | CATIII |
| Supply voltage / between the outer conductors / at AC / maximum permissible | 831 V |
| Consumed active power / for current measurement / per phase | 2.5 mW |
| Continuous current / at AC / maximum permissible | 10 A |
| Measuring category / for current measurement | CATIII |
| Zero-point suppression / for current measurement | 0 ... 10 % |
| for neutral conductor current | 0.0 % to 10.0 % (from Vrated, Irated) |
| Relative measurable current / at AC | |
| minimum | 1 % |
| maximum | 200 % |
| Apparent power consumption / for current measurement | |
| with measuring range 5 A / per phase | 2 V·A |
| Measuring procedure / for current measurement | TRMS |
| Measurable current / 1 / at AC / Rated value | 1 A |
| Connections |
| Type of connectable conductor cross-sections | |
| at the measurement inputs for voltage / at AWG conductors / solid | Screw connection |
| at the measurement inputs for voltage / solid | 2.5 mm² |
| at the measurement inputs for voltage / finely stranded / with core end processing | 2.5 mm² |
| at the measurement inputs for current / at AWG conductors / solid | Screw connection |
| Type of electrical connection | |
| at the inputs for supply voltage | screw-type terminals |
| at the measurement inputs for voltage | screw-type terminals |
| at the measurement inputs for current | screw-type terminals |
| of the fast Ethernet interface | RJ45 (8P8C) |
| Mechanical Design |
| Mounting position | vertical |
| Mounting type / panel mounting | No |
| Net weight | 754 g |
| Environmental conditions |
| Degree of pollution | 2 |
| Installation altitude / at height above sea level / maximum | 2 000 m |
| Standard | |
| for EMC for industrial sector | IEC 61000-6-2 |
| for EMC against unloading | IEC 61000-4-2 - 6 kV contact discharge; 8 kV air discharge |
| for EMC against high frequency fields | IEC 61000-4-3 80 MHz up to 3 GHz, 10 Vm |
| for EMC against conducted LF disturbance variables (industry) | IEC 61000-6-4 |
| for EMC against conducted disturbance variables via HF fields | IEC 61000-4-6; 2008; 0.15 MHz - 80 MHz |
| for EMC against magnetic fields with power engineering frequencies | IEC 61000-4-8, Class IV |
| for EMC against quick, transient electrical disturbances | IEC 61000-4-4 Class 3; 2 kV, 5 KHz |
| for EMC against voltage drops and interruptions | IEC 61000-4-11; 2004-03 |
| for EMC against surge voltages | IEC 61000-4-5 installation class 2, 2 kV/1 kV, |
| for free fall | IEC 60068-2-31 |
| for cyclic, environmental damp heat check | IEC 60068-2-78 Test Ca |
| for environmental coldness check | IEC 60068-2-1 Test Ad |
| for environmental dry heat check | IEC 60068-2-2 Test Bd |
| Relative humidity / at 25 °C / without condensation / during operation | |
| minimum | 75 % |
| maximum | 95 % |
| Ambient temperature | |
| during operation / minimum | -25 °C |
| during operation / maximum | 55 °C |
| during storage / minimum | -40 °C |
| during storage / maximum | 70 °C |