6AG1333-4BA00-7AA0
SIPLUS S7-1500 PM 1507 24V/8A

From SIEMENS

SIPLUS S7-1500 PM 1507 24V/8A
SIPLUS S7-1500 PM 1507 24 V/8 A -40 ... +70°C with conformal coating based on 6EP1333-4BA00 . STABILIZED POWER SUPPLY FOR SIMATIC S7-1500 INPUT: 120/230 V AC OUTPUT: 24 V/8 A DC
Input
Input1-phase AC
NoteAutomatic range selection
Supply voltage
1 at AC Rated value120 V
2 at AC Rated value230 V
Input voltage
1 at AC85 ... 132 V
2 at AC170 ... 264 V
Wide-range inputNo
Overvoltage resistance2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min.20 ms; at Vin = 93/187 V
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range45 ... 65 Hz
Input current
at rated input voltage 120 V3.7 A
at rated input voltage 230 V1.7 A
Switch-on current limiting (+25 °C), max.62 A
Duration of inrush current limiting at 25 °C
maximum3 ms
I²t, max.12 A²·s
Built-in incoming fuseT 6.3 A/250 V (not accessible)
Protection in the mains power input (IEC 898)Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C
Output
OutputControlled, isolated DC voltage
Rated voltage Vout DC24 V
Total tolerance, static ±1 %
Static mains compensation, approx.0.1 %
Static load balancing, approx.0.1 %
Residual ripple peak-peak, max.50 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)150 mV
Product function Output voltage adjustableNo
Status displayLED green for 24 V OK; LED red for error; LED yellow for stand-by
On/off behaviorNo overshoot of Vout (soft start)
Startup delay, max.1.5 s
Voltage rise, typ.10 ms
Rated current value Iout rated8 A
Current range0 ... 8 A
Supplied active power typical192 W
Short-term overload current
on short-circuiting during the start-up typical35 A
at short-circuit during operation typical35 A
Duration of overloading capability for excess current
on short-circuiting during the start-up70 ms
at short-circuit during operation70 ms
Parallel switching for enhanced performanceNo
Efficiency
Efficiency at Vout rated, Iout rated, approx.90 %
Power loss at Vout rated, Iout rated, approx.21 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.2 %
Dynamic load smoothing (Iout: 10/90/10 %), Uout ± typ.3 %
Load step setting time 10 to 90%, typ.5 ms
Load step setting time 90 to 10%, typ.5 ms
Setting time maximum5 ms
Protection and monitoring
Output overvoltage protectionAdditional control loop, limitation (closed loop control) at < 28.8 V
Current limitation8.4 ... 9.6 A
Current limitation, typ.9 A
Property of the output Short-circuit proofYes
Short-circuit protectionElectronic shutdown, automatic restart
Overload/short-circuit indicator-
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2
Protection classClass I
Leakage current
maximum3.5 mA
typical1.3 mA
CE markYes
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-40 ... +70 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3, no condensation
Relative humidity with condensation maximum100 %; Relative humidity, incl. condensation/frost permitted (no commissioning under condensation conditions)
Resistance to biologically active substances conformity acc. to EN 60721-3-3Yes
Resistance to chemically active substances conformity acc. to EN 60721-3-3Yes
Resistance to mechanically active substances conformity acc. to EN 60721-3-3Yes
Mechanics
Connection technologyScrew-/spring clamp connection
Connections
Supply inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
OutputL+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
Product function
removable terminal at inputYes
removable terminal at outputYes
Width of the enclosure75 mm
Height of the enclosure147 mm
Depth of the enclosure129 mm
Required spacing
top40 mm
bottom40 mm
left0 mm
right0 mm
Weight, approx.0.74 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationCan be mounted onto S7-1500 rail
MTBF at 40 °C1 362 918 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links